Yle follows: Investigation of three young spirit requires from the cottage fire ready – AIB of 4 recommendation the rent of the cottages to improve safety

the accident investigation board today gave the new recommendations of the rent of the cottages to improve safety. The background is Kittilä at Levi in April oc

- 27 reads.

Yle follows: Investigation of three young spirit requires from the cottage fire ready – AIB of 4 recommendation the rent of the cottages to improve safety

the accident investigation board today gave the new recommendations of the rent of the cottages to improve safety. The background is Kittilä at Levi in April occurred in the cottage fire, where the three minor children died.

you Can follow it on the briefing straight from this article at 9: 30 am onwards.

the Investigation of the cabin fire is now completed. Already it is reported that the fires were caused by improperly installed floor heating cables.

the burnt cottage was completed in 2005, a two-story log cabin. The cabin was on fire the moment the same pyhtääläisen a family of four siblings.

a child of three was asleep when the fire broke out upstairs. The oldest child, a teenage son, was sleeping downstairs, woke up the fire alarm out loud and managed to save themselves. Upstairs sleeping children die of smoke gas.

Read more:

Levi catastrophic cabin fire started faulty installation of the floor heating cable – AIB: "Can happen, unfortunately, to re -"

April, during the fire in Kittilä Levi destroyed the cottage was rent used and completed in 2005.YleAsennusvirhe made it possible to fire

the ntsb investigation resulted in a 't quite yet said in the spring that back at the cabin used in the floor heating of the allotment is a cottage in use in general. Quite yet considered the possibility that the accident could be repeated.

the wood floor below the heating cable was installed too tightly kinked and the insulation materials were damaged, which allowed the cable overheating and fire.

accident centre drew the attention of the rental cottages on the safety of attention immediately after the fire in the spring and found that the accommodation maximizes the upstairs building with loft can lead to a situation where the second floor of the premises is difficult or even impossible to remove in the case of fire.

the electricity safety regulations is turmamökin after the completion of the tightened. Floor heating cable the installation must now use fault current protection. It could have prevented the fire.

see also:

Three children of the spirit demanded levi's cabin fire lit up floor heating which flocks will easily become a death trap

the Faulty floor heating led to a three-minor die Levi – 6 questions and answers from the floor heating safety

Friends say goodbye to levi's cabin fire in the dead of young letters that they left the empty school desks – "Today is crying a lot"

Subscribe Yle newsletters! Proceed to order
Avatar
Your Name
Post a Comment
Characters Left:
Your comment has been forwarded to the administrator for approval.×
Warning! Will constitute a criminal offense, illegal, threatening, offensive, insulting and swearing, derogatory, defamatory, vulgar, pornographic, indecent, personality rights, damaging or similar nature in the nature of all kinds of financial content, legal, criminal and administrative responsibility for the content of the sender member / members are belong.